Type K thermocouple table
Type K probes whose output follows the type K thermocouple table
Exactly which voltage a NiCr-Ni probe produces at each temperature is fixed by the type K thermocouple table in IEC 60584-1, published in Germany as DIN EN 60584-1. Therma has been building such probes in Lindlar since 1991, assembling every element by hand within a quality management system certified to ISO 9001. In practice, the values on this page apply unchanged to every type K probe you order from us.
Design and diameter have no effect on the type K thermocouple table. Whether sheathed, screw-in or surface probe, the thermovoltage comes solely from the pairing of nickel-chromium and nickel. You configure our type K sheathed thermocouples in the shop by length, sheath material and termination.
Since one type K thermocouple table covers all designs, you can replace a probe without readjusting the controller or your evaluation. Most standard versions are in stock and usually reach you after about a week. Non-standard dimensions are built to your specification and are usually ready after one to two weeks.
Reference values of the type K thermocouple voltage chart up to 1,372 °C
The standard covers the range between minus 270 and 1,372 °C, referenced to a cold junction at exactly 0 °C. For everyday work, a few points taken from the type K thermocouple table at 200 K intervals are usually enough. With them you estimate the voltage at your measuring point, check a display or verify a controller. The sensitivity column shows how much voltage a single kelvin produces at that point. It helps you estimate intermediate values:
| Temperature | Thermocouple voltage in mV | Tolerance class 1 | Tolerance class 2 |
|---|---|---|---|
| minus 200 °C | minus 5.891 | not specified | not specified |
| minus 100 °C | minus 3.554 | not specified | not specified |
| 0 °C | 0.000 | ±1.5 K | ±2.5 K |
| 100 °C | 4.096 | ±1.5 K | ±2.5 K |
| 200 °C | 8.138 | ±1.5 K | ±2.5 K |
| 400 °C | 16.397 | ±1.6 K | ±3.0 K |
| 600 °C | 24.905 | ±2.4 K | ±4.5 K |
| 800 °C | 33.275 | ±3.2 K | ±6.0 K |
| 1,000 °C | 41.276 | ±4.0 K | ±7.5 K |
| 1,200 °C | 48.838 | not specified | ±9.0 K |
| 1,372 °C | 54.886 | not specified | not specified |
Between 0 and 1,000 °C the sensitivity only moves between 39 and 43 µV/K. That is why the K type thermocouple chart forms an almost straight line in this range. Below zero, the curve flattens noticeably. Under minus 100 °C, type T or a Pt100 is the better choice for precise measurements.
If your reading falls between two rows, divide the distance to the lower point by the sensitivity. At 10.000 mV you are 1.862 mV above the value for 200 °C, and dividing by 40 µV/K gives just over 46 K. The result of about 246 °C lies less than 0.5 K from the exact standard value. Many technicians keep a printed mV to temperature chart type K in the control cabinet for exactly this kind of quick estimate.
For tighter work, use the complete type K thermocouple reference table in 1 K steps. To rule out transcription errors, we calculate these values directly from the ITS-90 reference polynomials.
Images of Type K thermocouples
Type K Thermocouple Table
| Temperature | Thermocouple voltage in mV | Tolerance class 1 | Tolerance class 2 |
|---|---|---|---|
| minus 200 °C | minus 5.891 | not specified | not specified |
| minus 100 °C | minus 3.554 | not specified | not specified |
| 0 °C | 0.000 | ±1.5 K | ±2.5 K |
| 100 °C | 4.096 | ±1.5 K | ±2.5 K |
| 200 °C | 8.138 | ±1.5 K | ±2.5 K |
| 400 °C | 16.397 | ±1.6 K | ±3.0 K |
| 600 °C | 24.905 | ±2.4 K | ±4.5 K |
| 800 °C | 33.275 | ±3.2 K | ±6.0 K |
| 1,000 °C | 41.276 | ±4.0 K | ±7.5 K |
| 1,200 °C | 48.838 | not specified | ±9.0 K |
| 1,372 °C | 54.886 | not specified | not specified |
Cable lug | Fibreglass | Type K
20,55 €Sheathing tube | Teflon | Type K
17,35 €Spring loaded | Copper | Type K
37,68 €Other resistance thermometers
Reference junction compensation for the K type thermocouple millivolt chart
A thermocouple always measures a difference. The voltage at the terminals depends on the temperature difference between the measuring tip and the terminals, known as the reference junction or cold junction. Because the type K thermocouple table assumes 0 °C at that junction, you have to account for its actual temperature.
How large the effect is becomes clear in a worked example. Your voltmeter shows 15.397 mV while the terminals sit at 25 °C. These 25 °C correspond to 1.000 mV in the K type thermocouple millivolt chart, and you add this value to the reading before looking it up. Only the sum of 16.397 mV gives the correct temperature of 400 °C. Without correction, the type K thermocouple table would return about 376 °C, which is 24 K too low.
Modern transmitters and displays handle this compensation automatically. Many instruments sense the terminal temperature with a built-in sensor right at the input sockets. Our precision thermometer for NiCr-Ni already applies the type K thermocouple voltage chart internally. When you want to sanity-check a value at the plant, a look at the figures still helps.
Thermocouple wire or compensating cable between probe and instrument
Wherever two different metals meet, an additional thermovoltage forms. If you run the line from probe to instrument in copper, the transition creates an extra reference junction at an unknown temperature. The result: the reading departs from the type K thermocouple table without the error ever becoming visible.
A thermocouple wire, also called extension cable, consists of the same alloys as the thermocouple itself. It extends the measuring chain without changing its reference to the standard. Our type K thermocouple wire comes with PTFE, fibreglass or Kapton insulation and is rated class 1 under DIN EN 60584-3.
A compensating cable, by contrast, only reproduces the thermovoltage over a limited temperature range and reaches class 2. If it is heated beyond that range, for example right next to a furnace, its signal drifts away from the type K thermocouple table. It suits long runs at moderate temperatures into the control cabinet.
To close the chain, use green-coded connectors to DIN EN 50212 so the signal stays true to the type K thermocouple table.
Handmade type K probes from Lindlar with a free test report
Every probe from our production comes with a free test report. Against the type K thermocouple table, class 1 permits at most 1.5 K between minus 40 and 375 °C. Above that, the limit is 0.4 % of the measured temperature. If you want to know the actual deviation at your test points, order a calibration at the same time.
Depending on the product, you select factory calibration directly in the configurator. For thermocouples up to 1,200 °C, a DAkkS calibration accredited to ISO/IEC 17025 is also available. The certificate lists your readings point by point next to the type K thermocouple table. Details on test points and procedure are on our page about thermocouple calibration.
Need a probe the shop configurator cannot build? A drawing or STEP file is all our engineering team in Lindlar needs to check feasibility. A special design still follows the type K thermocouple table as long as the NiCr-Ni pairing stays unchanged. You can reach us by phone on +49 2266 487330-30.